Vega VEGAFLEX 83 Modbus and Levelmaster protocol PFA in Manual do Utilizador Página 80

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 96
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 79
80
11 Supplement
VEGAFLEX 83 • Modbus and Levelmaster protocol
41838-EN-130314
Response:
Parameter Length Code/Data
Function Code 1 Byte 0x11
Byte Number 1 Byte
Slave ID 1 Byte
Run Indicator Status 1 Byte
FC43Sub14,ReadDeviceIdentication
With this function code, the Device Identication can be queried.
Request:
Parameter Length Code/Data
Function Code 1 Byte 0x2B
MEI Type 1 Byte 0x0E
Read Device ID Code 1 Byte 0x01 to 0x04
Object ID 1 Byte 0x00 to 0xFF
Response:
Parameter Length Code/Data
Function Code 1 Byte 0x2B
MEI Type 1 Byte 0x0E
Read Device ID Code 1 Byte 0x01 to 0x04
Conrmity Level 1 Byte 0x01, 0x02, 0x03, 0x81, 0x82, 0x83
More follows 1 Byte 00/FF
Next Object ID 1 Byte Object ID number
Number of Objects 1 Byte
List of Object ID 1 Byte
List of Object length 1 Byte
List of Object value 1 Byte Depending on the Object ID
11.5 Levelmaster commands
The VEGAFLEX 83 is also suitable for connection to the following RTUs with Levelmaster protocol.
The Levelmaster protocol is often called "Siemens" "Tank protocol".
RTU Protocol
ABB Totalow Levelmaster
Kimray DACC 2000/3000 Levelmaster
Thermo Electron Autopilot Levelmaster
Parameters for the bus communication
The VEGAFLEX 83 is preset with the default values:
Vista de página 79
1 2 ... 75 76 77 78 79 80 81 82 83 84 85 ... 95 96

Comentários a estes Manuais

Sem comentários