12
5 Set up with the display and adjustment module
VEGABAR 81 • Slave sensor for electronic dierential pressure
46331-EN-131125
Enter the percentage value and the corresponding pressure value for
the max. level.
The quick setup for level measurement is nished.
4. Position correction
In this menu item you compensate the inuence of the installation
position of the instrument (oset) on the measured value.
5. Min. adjustment
In this menu item you carry out the min. adjustment for ow.
Enter the percentage value and the corresponding pressure value for
the min. ow.
6. Max. adjustment
In this menu item you carry out the max. adjustment for ow.
Enter the percentage value and the corresponding pressure value for
the max. ow.
7. Linearization
In this menu item, you select the characterics of the output signal.
The quick setup for ow measurement is nished.
4. Unit, static pressure
In this menu item, you determine the unit of the static, i.e. superim-
posed pressure.
5. Position correction
In this menu item you compensate the inuence of the installation
position of the instrument (oset) on the measured value.
6. zero adjustment
In this menu item you carry out the zero adjustment for the dierential
pressure.
Enter the respective pressure value for 0 %.
7. span adjustment
In this menu item you carry out the span adjustment for the dierential
pressure
Enter the respective pressure value for 100 %.
Quick setup - Flow meas-
urement
Quick setup - Dierential
pressure measurement