12
5 Set up with the display and adjustment module
VEGABAR 81 • Slave sensor for electronic dierential pressure
46331-EN-131125
Enter the percentage value and the corresponding pressure value for
the max. level.
The quick setup for level measurement is nished.
4. Position correction
In this menu item you compensate the inuence of the installation
position of the instrument (oset) on the measured value.
5. Min. adjustment
In this menu item you carry out the min. adjustment for ow.
Enter the percentage value and the corresponding pressure value for
the min. ow.
6. Max. adjustment
In this menu item you carry out the max. adjustment for ow.
Enter the percentage value and the corresponding pressure value for
the max. ow.
7. Linearization
In this menu item, you select the characterics of the output signal.
The quick setup for ow measurement is nished.
4. Unit, static pressure
In this menu item, you determine the unit of the static, i.e. superim-
posed pressure.
5. Position correction
In this menu item you compensate the inuence of the installation
position of the instrument (oset) on the measured value.
6. zero adjustment
In this menu item you carry out the zero adjustment for the dierential
pressure.
Enter the respective pressure value for 0 %.
7. span adjustment
In this menu item you carry out the span adjustment for the dierential
pressure
Enter the respective pressure value for 100 %.
Quick setup - Flow meas-
urement
Quick setup - Dierential
pressure measurement