Operating InstructionsPressure transmitter with MINI-CERTEC® measuring cellVEGABAR 544 … 20 mA/HARTDocument ID: 36726
103 Product descriptionVEGABAR 54 • 4 … 20 mA/HART36726-EN-130321The delivery must be checked for completeness and possible transit damage immediately
113 Product descriptionVEGABAR 54 • 4 … 20 mA/HART36726-EN-130321Youcanndadditionalinformationinthesupplementaryinstructionsmanual"Fla
124 MountingVEGABAR 54 • 4 … 20 mA/HART36726-EN-1303214 Mounting4.1 General instructionsMake sure that all parts of the instrument coming in direct c
134 MountingVEGABAR 54 • 4 … 20 mA/HART36726-EN-13032121212112Fig. 4: Position of the lter element1 Filter element2 Blind plugCaution:Duetothel
144 MountingVEGABAR 54 • 4 … 20 mA/HART36726-EN-1303214.2 Mounting stepsFormountingVEGABAR54,aweldedsocketisrequired.Youcanndthesecompo
154 MountingVEGABAR 54 • 4 … 20 mA/HART36726-EN-130321Tip:Mount the wall mounting plate so that the cable entry of the socket housing points downward.
165 Connecting to power supplyVEGABAR 54 • 4 … 20 mA/HART36726-EN-1303215 Connecting to power supply5.1 Preparing the connectionAlways keep in mind
175 Connecting to power supplyVEGABAR 54 • 4 … 20 mA/HART36726-EN-130321housing.Thiswouldinuencethestabilityoftheconnectionandthetightness
185 Connecting to power supplyVEGABAR 54 • 4 … 20 mA/HART36726-EN-1303218. Press down the opening levers of the terminals, you will hear the terminal
195 Connecting to power supplyVEGABAR 54 • 4 … 20 mA/HART36726-EN-130321321Fig. 8: Components of the external housing1 Screws2 Wall mounting plate3
2ContentsVEGABAR 54 • 4 … 20 mA/HART36726-EN-130321Contents1 About this document1.1 Function ...
205 Connecting to power supplyVEGABAR 54 • 4 … 20 mA/HART36726-EN-130321I²CDisplay12 56783412Fig. 9: Electronics and connection compartment, single ch
215 Connecting to power supplyVEGABAR 54 • 4 … 20 mA/HART36726-EN-130321132Display12 5678I2CFig. 11: Electronics compartment, double chamber housing1
225 Connecting to power supplyVEGABAR 54 • 4 … 20 mA/HART36726-EN-130321I2C112Fig. 13: Wiring plan, double chamber housing1 Voltage supply, signal ou
235 Connecting to power supplyVEGABAR 54 • 4 … 20 mA/HART36726-EN-130321567812DisplayI²C21543Fig. 16: Electronics and connection compartment1 Spring-
245 Connecting to power supplyVEGABAR 54 • 4 … 20 mA/HART36726-EN-1303211234634125Fig. 17: Connection of the sensor in the housing socket1 Brown2 Bl
255 Connecting to power supplyVEGABAR 54 • 4 … 20 mA/HART36726-EN-130321Then the corresponding current is outputted to the cable (the value correspond
266 Set up with the display and adjustment module PLICSCOMVEGABAR 54 • 4 … 20 mA/HART36726-EN-1303216 Set up with the display and adjustment module P
276 Set up with the display and adjustment module PLICSCOMVEGABAR 54 • 4 … 20 mA/HART36726-EN-130321Fig. 19: Insert display and adjustment moduleNote:
286 Set up with the display and adjustment module PLICSCOMVEGABAR 54 • 4 … 20 mA/HART36726-EN-130321 – Save value• [->] key to select: – Menu chang
296 Set up with the display and adjustment module PLICSCOMVEGABAR 54 • 4 … 20 mA/HART36726-EN-130321Information:The steps 1, 3 and 4 are not necessary
3ContentsVEGABAR 54 • 4 … 20 mA/HART36726-EN-1303218 Maintenanceandfaultrectication8.1 Maintain ...
306 Set up with the display and adjustment module PLICSCOMVEGABAR 54 • 4 … 20 mA/HART36726-EN-1303214. Conrmwith[OK],thesubmenu"Density un
316 Set up with the display and adjustment module PLICSCOMVEGABAR 54 • 4 … 20 mA/HART36726-EN-1303214. Set the requested mbar value with [+] and [-&g
326 Set up with the display and adjustment module PLICSCOMVEGABAR 54 • 4 … 20 mA/HART36726-EN-130321Inthemenuitems"zero"and"span&
336 Set up with the display and adjustment module PLICSCOMVEGABAR 54 • 4 … 20 mA/HART36726-EN-130321UnitUnitofmeasurementbar▼Temperature unit°C▼3.
346 Set up with the display and adjustment module PLICSCOMVEGABAR 54 • 4 … 20 mA/HART36726-EN-130321Information:Thezeroadjustmentshiftsthevalueo
356 Set up with the display and adjustment module PLICSCOMVEGABAR 54 • 4 … 20 mA/HART36726-EN-130321• SIL• HART mode6)• PIN• ApplicationCopy sensor da
366 Set up with the display and adjustment module PLICSCOMVEGABAR 54 • 4 … 20 mA/HART36726-EN-130321Menu section Function ResetvalueDamping 1 sLinear
376 Set up with the display and adjustment module PLICSCOMVEGABAR 54 • 4 … 20 mA/HART36726-EN-130321Basic adjustment▶Basic adjustment 1DisplayDiagnost
386 Set up with the display and adjustment module PLICSCOMVEGABAR 54 • 4 … 20 mA/HART36726-EN-130321ServiceBasic adjustment 4DisplayDiagnostics▶Servic
397 Set up with PACTware and other adjustment programsVEGABAR 54 • 4 … 20 mA/HART36726-EN-1303217 Set up with PACTware and other adjustment programs7
41 About this documentVEGABAR 54 • 4 … 20 mA/HART36726-EN-1303211 About this document1.1 FunctionThis operating instructions manual provides all the
407 Set up with PACTware and other adjustment programsVEGABAR 54 • 4 … 20 mA/HART36726-EN-13032112 43OPENTWISTUSBLOCKFig. 23: Connecting the PC via HA
417 Set up with PACTware and other adjustment programsVEGABAR 54 • 4 … 20 mA/HART36726-EN-1303217.3 Parameter adjustment with AMS™ and PDMFor VEGA se
428MaintenanceandfaultrecticationVEGABAR 54 • 4 … 20 mA/HART36726-EN-1303218 Maintenanceandfaultrectication8.1 MaintainIf the instrument is
438MaintenanceandfaultrecticationVEGABAR 54 • 4 … 20 mA/HART36726-EN-130321Error code Cause Rectication4 … 20 mA signal not stableLeveluctuati
448MaintenanceandfaultrecticationVEGABAR 54 • 4 … 20 mA/HART36726-EN-130321Fperf=√((FT)2 + (FKl)2 (+ Fa)2)With:• Ftotal: Total deviation• Fperf
458MaintenanceandfaultrecticationVEGABAR 54 • 4 … 20 mA/HART36726-EN-130321Total deviation analogue output signal absolute:Ftotal = 0.70 % x 8 ba
468MaintenanceandfaultrecticationVEGABAR 54 • 4 … 20 mA/HART36726-EN-130321data and displays the actual hardware and software version of the sens
479 DismountingVEGABAR 54 • 4 … 20 mA/HART36726-EN-1303219 Dismounting9.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process
4810 SupplementVEGABAR 54 • 4 … 20 mA/HART36726-EN-13032110 Supplement10.1 Technical dataGeneral dataParameter, pressure Gauge pressure, absolute pre
4910 SupplementVEGABAR 54 • 4 … 20 mA/HART36726-EN-130321 Ʋ Transport cover PFAWeight approx.0.8 … 8 kg (1.764 … 17.64 lbs), depending on process tti
52 For your safetyVEGABAR 54 • 4 … 20 mA/HART36726-EN-1303212 For your safety2.1 Authorised personnelAll operations described in this operating inst
5010 SupplementVEGABAR 54 • 4 … 20 mA/HART36726-EN-130321Damping (63 % of the input variable) 0 … 999 s, adjustableAdditional output parameter - tempe
5110 SupplementVEGABAR 54 • 4 … 20 mA/HART36726-EN-130321Nominalrange Overload capacity, max. pressureOverload capacity, min. pres-sure-1 … +10 bar/-
5210 SupplementVEGABAR 54 • 4 … 20 mA/HART36726-EN-130321Nominalrange Overload capacity, max. pressureOverload capacity, min. pres-sure-3 … +3 psig +
5310 SupplementVEGABAR 54 • 4 … 20 mA/HART36726-EN-130321 Ʋ Turn down 1 : 1 up to 5 : 1 < 0.1 %/10 K Ʋ Turn down up to 10 : 1 < 0.15 %/10 KOutsi
5410 SupplementVEGABAR 54 • 4 … 20 mA/HART36726-EN-130321 Ʋ PMC 316L PN 10 Ʋ Flange 316L PN 40Product temperature depending on the measuring cell seal
5510 SupplementVEGABAR 54 • 4 … 20 mA/HART36726-EN-130321Electromechanicaldata-versionIP66/IP68(1bar)Cable entry Ʋ Single chamber housing – 1
5610 SupplementVEGABAR 54 • 4 … 20 mA/HART36726-EN-130321Protection rating Ʋ unassembled IP 20 Ʋ mounted into the sensor without cover IP 40Material Ʋ
5710 SupplementVEGABAR 54 • 4 … 20 mA/HART36726-EN-130321Overvoltage category IIIProtection class IIFunctionalsafety(SIL)Functionalsafetyisalread
5810 SupplementVEGABAR 54 • 4 … 20 mA/HART36726-EN-130321Aluminium housing21ø 86 mm (3.39")~ 116 mm (4.57")116 mm (4.57")M20x1,5M20x1,5
5910 SupplementVEGABAR 54 • 4 … 20 mA/HART36726-EN-130321Stainless steel housing~ 69 mm(2.72")ø 79 mm(3.11")117 mm (4.61")M20x1,5/½ NPT
62 For your safetyVEGABAR 54 • 4 … 20 mA/HART36726-EN-1303212.6 CE conformityThisdevicefulllsthelegalrequirementsoftheapplicableECguide-li
6010 SupplementVEGABAR 54 • 4 … 20 mA/HART36726-EN-130321External housing with version IP 681265 mm(2.68")68 mm(2.68")92 mm(3.62")42mm(
6110 SupplementVEGABAR 54 • 4 … 20 mA/HART36726-EN-130321VEGABAR54,threadedttingGAGDGB22 mm(0.87")59 mm(2.32")40 mm(1.58")44 mm(1.7
6210 SupplementVEGABAR 54 • 4 … 20 mA/HART36726-EN-130321VEGABAR54,hygienictting1RI44,5 mm(1.75")G1 AGK67,5 mm(2.66")ø 52 mm (2.05"
6310 SupplementVEGABAR 54 • 4 … 20 mA/HART36726-EN-130321VEGABAR54,hygienictting2ø 62,5 mm(2.46")45 mm(1.77")REFig. 36: VEGABAR 54, hyg
6410 SupplementVEGABAR 54 • 4 … 20 mA/HART36726-EN-130321VEGABAR54,angeconnection1DB, FZ, DA, F1d4kd2Dfb50 mm(1.97")DNmmPN DkbDB 15 40 95 16
6510 SupplementVEGABAR 54 • 4 … 20 mA/HART36726-EN-130321VEGABAR54,angeconnection2d2d4kDfbFA47,8 mm(1 7/8")2 43/64" 5/64"4xø 35/64
6610 SupplementVEGABAR 54 • 4 … 20 mA/HART36726-EN-130321VEGABAR54,connectionforpaperindustry145,5 mm(1 51/64")ø 26,3 mm (1 1/32")ø 36
6710 SupplementVEGABAR 54 • 4 … 20 mA/HART36726-EN-130321VEGABAR54,connectionforpaperindustry2VP VR ø 29,3 mm (1 5/32")30 mm(1 3/16")1
6810 SupplementVEGABAR 54 • 4 … 20 mA/HART36726-EN-13032110.3 Industrial property rightsVEGA product lines are global protected by industrial propert
69INDEXVEGABAR 54 • 4 … 20 mA/HART36726-EN-130321INDEXAAccessories – Display and adjustment module 10 – External display and adjustment unit 10 – Ex
73 Product descriptionVEGABAR 54 • 4 … 20 mA/HART36726-EN-1303213 Product description3.1 CongurationThe scope of delivery encompasses:• VEGABAR 54
70NotesVEGABAR 54 • 4 … 20 mA/HART36726-EN-130321
71NotesVEGABAR 54 • 4 … 20 mA/HART36726-EN-130321
Printing date:VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermany36726-EN-130321All statements concerning scope of delivery, application, practi
83 Product descriptionVEGABAR 54 • 4 … 20 mA/HART36726-EN-1303212113105436789111214Fig. 2: Layout of the type label (example)1 Instrument type2 Prod
93 Product descriptionVEGABAR 54 • 4 … 20 mA/HART36726-EN-130321The CERTEC® measuring cell is also equipped with a temperature sensor. The temperature
Comentários a estes Manuais